Product Details
Related Product Model Recommendations
| 3BHE046836R0102 |
3BHE013088R001 |
3BHE014135R0011 |
| 3BHE027632R0101 |
3BHE014070R0101 |
3BHE037864R0108 |
| 3BSE082896R1 PM858K02 |
3BHE030579R0003 |
3BHE041626R0101 |
| 3BHE009681R0101 5SHY4045L0001 |
3BHE024747R0101 |
3BHE032025R1101 |
| 3BHE030579R0003 |
3BHE024855R0101 |
3BHE024313R0101 |
| 3BHB003041R0101 |
3BHE032025R1101 |
3BHE008128R0001 |
| 3BHB004661R0101 |
3BHE021887R0101 |
3BSE050091R65 |
| 3BHB018162 |
3BHE024577R0101 |
3BHE009319R0001 |
| 3BHB003041R0101 UFC719AE01 |
3BHB003041R0101 |
3BHE020455R0001 |
| 3BSE042238R2 PP846A |
3BHE022293R0101 |
3BHE025088R6618 |
| 3BSE004006R1 CI626V1 |
3PHE022287R0001 |
PHARPS3200000 |
| 3BSE018124R1 CI853K01 |
PM582-ETH |
PHBRC3000000 |
Payment & Delivery

FAQs

Q1: What is the key difference between AO845A and AO815?
The AO845A supports 1:1 redundancy (hot standby configuration), whereas the AO815 does not. Both support HART pass-through and 8 channels of 4...20 mA output. For high-availability systems where a module failure cannot be tolerated, AO845A with redundant MTU (TU842/TU852) is the recommended choice .
Q2: Which ABB control systems is the AO845A compatible with?
The AO845A is part of the S800 I/O system and is designed for ABB System 800xA DCS, AC 800M controllers, and Freelance systems .
Q3: How does redundancy work with the AO845A?
Two AO845A modules can be configured as a 1:1 redundant pair using a redundant MTU (TU842 or TU852). If the primary module fails (e.g., output circuit error, power supply issue), the system automatically switches to the standby module without interrupting the control signal to the field device .
Q4: Does the AO845A support HART communication?
Yes. Each of the 8 output channels features HART pass-through functionality, enabling two-way digital communication for remote configuration, calibration, and asset management of smart field instruments. The output filter must be enabled on channels used for HART communication .
Q5: What are the diagnostic capabilities of the AO845A?
The module performs cyclic self-diagnostics, reporting:
-
External Channel Error – process power supply too low or open circuit
-
Internal Channel Error – output circuit cannot deliver correct current
-
Module Error – output transistor error, short circuit, checksum error, internal power supply error, or watchdog error.