Stock New Original Triconex 3700A Triple Modular Redundant Analog Input Module

The Triconex 3700A is a 32-channel Triple Modular Redundant (TMR) Analog Input Module for the Tricon Safety Instrumented System (SIS). It provides 32 differential, DC-coupled input channels with a 0–5 VDC input range (plus 6% over-range), converting field analog signals into digital values for the three Main Processors using a mid-value selection (MVS) voting algorithm.

  • Item No :

    Triconex 3700A
  • Order(MOQ) :

    1 Piece
  • Payment :

    EXW/CIF
  • Product Origin :

    USA
  • Shipping Port :

    Wuhan
  • Lead Time :

    3-5days
  • Weight :

    3kg
  • Product Details

     
     
    Specification Description
    Manufacturer Triconex (Schneider Electric / Invensys)
    Model 3700A
    Product Type TMR Analog Input Module
    Input Channels 32 differential, DC-coupled 
    Input Voltage Range 0 to 5 VDC (+6% over-range, 0 to 5.3 VDC) 
    Input Current Range 0 to 20 mA (with 250 Ω shunt resistor) 
    Resolution 12 bits 
    Accuracy < 0.15% of Full Scale Range (FSR) from 0° to 60°C 
    Input Update Rate 55 ms 
    Input Resistance (Load) 30 MΩ (DC) minimum 
    Common Mode Rejection -80 dB (DC – 100 Hz) typical 
    Common Mode Range -12V to +12V peak 
    Channel-to-Channel Isolation 200 kΩ typical 
    Input Over-range Protection 150 VDC / 115 VAC continuous 
    Logic Power < 10 watts 
    Module Status Indicators Pass, Fault, Active 
    Diagnostics Continuous per-channel diagnostics; open/short circuit, over/under range detection 
    Hot-Spare Support Yes – online replacement 
    External Termination Requires separate External Termination Panel (ETP) with cable interface 
    Operating Temperature -40°C to +70°C (some sources indicate 0°C to +60°C) 
    Safety Certification SIL 3 (IEC 61508), TÜV certified 
    Weight Approx. 0.8–2.2 kg (varies by source) 
    Dimensions Approx. 40.5 × 2.0 × 40.0 cm 
    Country of Origin USA 

    Related Product Model Recommendations

     
     
    Model Description Typical Application
    3700A (this model) TMR Analog Input, 32-ch, 0–5 VDC Standard analog input for Tricon SIS
    3701 TMR Analog Input, 32-ch, 0–10 VDC  Higher voltage range applications
    3703E TMR Analog Input, 16-ch, 0–10 VDC, isolated  Isolated channel requirements
    3704E TMR Analog Input, high-density, 0–10 VDC  High-density applications
    3721 TMR Analog Input, 32-ch, 0–5 VDC or -5 to +5 VDC, 16-bit  Recommended replacement for 3700A with higher resolution
    3720 TMR Analog Input, single-ended, 0–5 VDC  Single-ended input applications
    HiSHPTB/32/TR-AI-01-Y1 Replacement FTA for Triconex 3700A and 3721  Required termination assembly

    FAQs

    Q1: What is the primary function of the Triconex 3700A?

    It is a 32-channel TMR analog input module that accepts differential voltage signals from field sensors (0–5 VDC), converts them to digital values, and transmits them to the three Tricon Main Processors. The processors use a mid-value selection (MVS) algorithm to determine the true value, ignoring any single channel that provides divergent or faulty readings.

    Q2: Can the 3700A directly measure 4–20 mA signals?

    No. The module itself measures 0–5 VDC. To measure 4–20 mA, you must use a Triconex termination panel with integrated precision 250 Ω shunt resistors to perform the current-to-voltage conversion.

    Q3: Does the 3700A support hot-swap?

    Yes. The module supports hot-spare capability, allowing online replacement of a faulty module without system interruption. The "ACTIVE" LED will blink during the synchronization process and remain steady once the module is fully online.

    Q4: What is the difference between the 3700 and the 3700A?

    The "A" version represents an enhanced hardware revision with improved component reliability and expanded diagnostic capabilities. It is fully backward compatible with the standard 3700 in most applications . The 3700A adds +6% over-range measurement capability (0 to 5.3 VDC) .

    Q5: What are the most common installation pitfalls?

    Key pitfalls include: (1) Missing or incorrect FTA – the module requires a separate External Termination Panel (ETP) with proper cable interface; (2) Shunt resistor configuration – for 4–20 mA signals, the termination panel must include 250 Ω precision resistors; (3) Chassis keying – each module is mechanically keyed for proper installation; ensure it is seated firmly in the correct slot.