New Original Stock Honeywell 900C72R-0100-44 C70R Redundant CPU Module

The Honeywell 900C72R-0100-44 is a C70R Redundant CPU module for the ControlEdge HC900 hybrid control system. The module supports seamless failover between primary (Lead) and backup (Reserve) CPUs, ensuring continuous operation for critical industrial processes. It provides dual Ethernet ports for network redundancy and RS-232/RS-485 serial interfaces for Modbus communication.

  • Item No :

    900C72R-0100-44
  • Order(MOQ) :

    1 Piece
  • Payment :

    EXW/CIF
  • Product Origin :

    USA
  • Shipping Port :

    Wuhan
  • Lead Time :

    3-5days
  • Weight :

    3kg
  • Product Details

     
     
    Item Specification
    Product Type Redundant CPU Controller Module
    Manufacturer Honeywell
    Model 900C72R-0100-44
    Series ControlEdge HC900
    CPU Class C70R
    Processor NetSilicon 9750 Microprocessor
    Redundancy Dual CPU with RSM-based failover management
    Communication Ports 2× Ethernet 10/100 Base-T
    Serial Communication RS-232 / RS-485 Modbus RTU
    Supported Protocols Modbus TCP/IP, OPC, Ethernet/IP
    Redundant Rack 900RR0-0001
    Required Module Redundancy Switch Module (RSM)
    Operating Temperature 0°C to +60°C
    Power Supply 5 VDC, 1500 mA max
    Weight Approx. 360 g

    Related Product Model Recommendations

     
     
    Model Product Type Application Scenario
    900C72R-0100-43 C70R Redundant CPU (alternate revision) Same C70R class; verify firmware compatibility before pairing
    900RR0-0001 Redundant Controller Rack Required for dual-CPU redundant configuration
    900RSM-0001 Redundancy Switch Module Manages failover between Lead and Reserve CPUs
    900C75S-0460-00 C75S SIL2 Redundant CPU Higher-performance SIL2 safety applications

    Frequently Asked Questions (FAQ)

    Q1: Does the 900C72R-0100-44 support redundant controller operation?
    A: Yes. The module supports dual CPU redundant configurations with failover management. It requires a 900RR0-0001 redundant CPU rack and a 900RSM-0001 redundancy switch module for complete redundancy functionality.

    Q2: What is the difference between the -43 and -44 revisions?
    A: The 900C72R-0100-43 and 900C72R-0100-44 are different hardware revisions of the same C70R CPU class. They share the same functional role but may have firmware or minor hardware differences. For redundant CPU pairs, both modules should match exactly in revision and firmware build.

    Q3: What communication interfaces does this module provide?
    A: It features dual 10/100 Base-T Ethernet ports for network redundancy and host communication, plus RS-232/RS-485 serial interfaces supporting Modbus RTU protocol.

    Q4: How does failover work between redundant CPUs?
    A: The Lead Controller performs all primary tasks including I/O communication and host interfacing. If a fault is detected, failover transfers all primary tasks to the Reserve Controller. Failure detection and failover execute in 4 analog control cycles or less.

    Q5: Can the CPU module be replaced while the system remains operational?
    A: The module supports hot-swap replacement in properly configured redundant setups. The Reserve CPU can be replaced while the Lead continues running. The RSM may also be replaced under power.