New Original Bently Nevada 3500/62 163179-03 Process Variable Monitor in Stock

The Bently Nevada 163179-03 is the main board (front card) for the 3500/62 Process Variable Monitor in the 3500 Machinery Protection System. It integrates non-vibration process parameters—such as pressure, flow, temperature, and level—into the 3500 rack's alarm and protection infrastructure.

  • Item No :

    163179-03
  • Order(MOQ) :

    1 Piece
  • Payment :

    EXW/CIF
  • Product Origin :

    USA
  • Shipping Port :

    Wuhan
  • Lead Time :

    3-5days
  • Weight :

    3kg
  • Product Details

     
     
    Specification Description
    Manufacturer Bently Nevada (Baker Hughes)
    Model 3500/62
    Part Number 163179-03
    Product Type Process Variable Monitor Main Board
    Number of Channels 6 independent analog input channels 
    Supported Inputs +4 to +20 mA current; -10 Vdc to +10 Vdc voltage 
    Input Impedance ±10V I/O: 1 MΩ; 4-20 mA I/O: 50 Ω 
    Isolation 500 V channel-to-ground (isolated I/O version) 
    Accuracy ±0.33% of full-scale typical; ±1% maximum 
    Update Rate 100 milliseconds 
    Alarm Setpoints Alert and Danger, adjustable 0-100% of full-scale 
    Alarm Delay Alert: 1-60 s in 1 s intervals; Danger: 1-60 s in 0.5 s intervals 
    Power Consumption 7.0 W typical 
    Front Panel LEDs OK, TX/RX, Bypass 
    Operating Temperature -30°C to +65°C (internal/external termination I/O); 0°C to +65°C (internal barrier I/O) 
    Storage Temperature -40°C to +85°C 
    Humidity 95%, non-condensing 
    Dimensions (H x W x D) 241.3 mm × 24.4 mm × 241.8 mm 
    Weight 0.82 kg (1.8 lb) 
    Rack Space 1 full-height front slot + 1 full-height rear I/O slot 
    Safety Certification SIL 2 (IEC 61508), TÜV certified 
    Compliance API 670 
    Country of Origin USA 

    Related Product Model Recommendations

     
     
    Model Description Typical Application
    163179-03 (this model) 3500/62 Process Variable Monitor Main Board Companion front card for all 3500/62 I/O modules
    136491-01 -10 to +10 Vdc I/O Module with Internal Terminations Voltage-input process monitoring with internal wiring 
    136499-01 -10 to +10 Vdc I/O Module with External Terminations Voltage-input process monitoring with external wiring 
    136294-01 Isolated 4-20 mA I/O Module with Internal Terminations Current-input process monitoring with internal wiring 
    136483-01 Isolated 4-20 mA I/O Module with External Terminations Current-input process monitoring with external wiring 
    137110-01 4-20 mA Intrinsically Safe Barrier I/O Module with Internal Terminations Hazardous area (intrinsically safe) applications 
    3500/60 Temperature Monitor RTD/TC temperature monitoring 
    3500/61 Temperature Monitor with Recorder Outputs Temperature monitoring with 4-20 mA retransmission 

    Frequently Asked Questions (FAQ)

    Q1: What is the primary function of the 163179-03?

    It is the main board for the 3500/62 Process Variable Monitor. It accepts 4-20 mA current or ±10 Vdc voltage inputs from industrial transmitters, conditions these signals, and compares them against user-programmable alarm setpoints (Alert and Danger). It monitors non-vibration parameters such as pressure, flow, temperature, and level.

    Q2: What I/O modules are compatible with the 163179-03?

    The 163179-03 works with multiple rear I/O module variants: 136491-01 (±10 Vdc, internal terminations), 136499-01 (±10 Vdc, external terminations), 136294-01 (isolated 4-20 mA, internal terminations), 136483-01 (isolated 4-20 mA, external terminations), and 137110-01 (4-20 mA with intrinsic safety barrier, internal terminations).

    Q3: Can the 163179-03 be used in a Triple Modular Redundant (TMR) configuration?

    Yes. For TMR applications, three identical 3500/62 modules must be installed adjacent to each other in the rack. The system uses two types of voting to ensure accurate operation and avoid single-point failures.

    Q4: Is the 163179-03 hot-swappable?

    Yes, the module supports hot-swap capability. However, during replacement, the six-channel process-variable measurement is temporarily invalid while other rack modules continue running normally. Before pulling or inserting the module, bypass active alarms to avoid accidental machine trips.

    Q5: What is the difference between the 3500/62 and the 3500/60/61?

    The 3500/62 is a Process Variable Monitor for pressure, flow, temperature, and level signals (4-20 mA / ±10 Vdc). The 3500/60 and 3500/61 are Temperature Monitors for RTD and thermocouple inputs. The 3500/61 provides recorder outputs (4-20 mA retransmission) per channel, while the 3500/60 does not. Main boards and I/O modules cannot be swapped between these monitor types.

Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
Leave A Message