PRODUCT SPECIFICATION
GM D1020D Powered Isolating Driver

FEATURES
SIL2 /SC3
Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
High Density, two channels per unit.
4-20 mA Input, Output Signal.
HART® compatible.
Input and Output short circuit proof.
High Accuracy.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1
In-field programmability by DIP Switch.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
APPLICATION
GM Repeater Power Supply is widely used in various scenarios that require enhanced wireless signal coverage, such as large offices, conference rooms,
warehouses, stadiums, etc. In these scenarios, repeaters amplify and forward wireless signals to improve the transmission distance and stability of the
network, so as to meet the communication needs of users.
Core Advantages
SIL 2 Certified Safety Integrity
The D1020D is certified to SIL 2 (SC 3) according to IEC 61508, with PFDavg (1 year) of 3.08 E-04 and SFF of 82.12%. G.M. International is TÜV-certified for safety-related systems up to SIL 3.
Hazardous Area Signal Transfer
The isolator transfers signals from Safe Area controllers to loads in Zone 0 (Zone 20), Division 1 hazardous areas. It can be installed in Zone 2, Division 2 locations, providing flexible deployment options for demanding process environments.
Bidirectional HART Communication
The circuit supports bidirectional communication signals within a 0.5 to 40 KHz frequency band (3 dB), fully compatible with HART and higher-frequency smart protocols. This enables remote configuration and diagnostics of smart valve positioners and I/P converters without breaking the isolation barrier.
High Output Capacity with Low Input Drop
The D1020D delivers 15 V at 20 mA output capacity while maintaining a low voltage drop of ≤ 2.0 V across its input terminals. This combination ensures reliable signal transmission even to high-resistance loads up to 750 Ω.
Field Open Circuit Detection
In the 4-20 mA input range, a field open circuit reflects a high impedance to the control device output circuit, providing inherent fault detection for critical safety loops.
High Density and Three-Port Isolation
With two independent channels per unit and 22.5 mm width, the D1020D maximizes panel density. Three-port isolation (input/output/supply) with 1.5 KV test voltage between I.S. output and both input and supply ensures robust galvanic separation.
HOT SELLING
|
VW3A98CTM01
|
6ES7314-5AE01-0AB0
|
22A-V1P5H204
|
773727
|
|
VW3A98ABPC1
|
6ES7314-5AE02-0AB0
|
22A-V1P5F104
|
773723
|
|
VW3A99ACFCB
|
6ES7314-5AE10-0AB0
|
22A-D8P7N104
|
773525
|
|
VW3A99ACA02
|
6ES7314-6BF00-0AB0
|
22A-D8P7F104
|
773602
|
|
VW3A99ACA03
|
6ES7314-6BG03-0AB0
|
22A-D6P0N104
|
773610
|
|
VX5FUPM0400
|
6ES7314-6CF02-0AB0
|
22A-D6P0H204
|
773631
|