New Original Stock Honeywell FTA-T-02 80363969-150 Fail-Safe Output Module

The Honeywell FTA-T-02  80363969-150 is a fail-safe digital output Field Termination Assembly (FTA) designed for Honeywell’s Safety Manager and FSC (Fail Safe Control) systems. It serves as the critical interface between System Interconnection Cables (SICs) and external field wiring, providing 24 output channels for safety-critical applications.

  • Item No :

    FTA-T-02 80363969-150
  • Order(MOQ) :

    1 Piece
  • Payment :

    EXW/CIF
  • Product Origin :

    USA
  • Shipping Port :

    Wuhan
  • Lead Time :

    3-5days
  • Weight :

    3kg
  • Product Details

     
     
    Item Specification
    Product Type Fail-Safe Digital Output Field Termination Assembly (FTA)
    Manufacturer Honeywell
    Model Designation FTA-T-02
    Part Number 80363969-150
    Compatible Systems Safety Manager, FSC, TPS/Experion PKS
    Number of Channels 24 (6 groups of 4 channels each)
    Supported Output Voltage 24 / 48 / 60 VDC
    Maximum Continuous Current 2 A per channel
    Maximum Voltage (IEC 1010) 36 VAC / 50 VDC (Cat. III); 125 VAC / 150 VDC (Cat. II)
    Terminal Type Screw terminals (max. AWG 14 / 2.5 mm²)
    Strip Length 0.7 cm (0.28 in)
    Tightening Torque 0.5 Nm (0.37 ft-lb)
    Mounting DIN EN rail TS32 / TS35 × 7.5
    Used Rail Length 14.6 cm (5.75 in)
    Dimensions (L × W × H) 14.5 × 7 × 5.7 cm
    Weight Approx. 0.2–0.4 kg
    Approvals CE, UL
    Operating Temperature -20°C to +70°C

    Related Product Model Recommendations

     
     
    Model Product Type Application Scenario
    FTA-T-01 8-Channel Fail-Safe Output FTA Lower-density safety output applications
    FTA-T-03 32-Channel Fail-Safe Output FTA High-density safety output configurations
    FTA-A-02 Analog Input FTA Analog signal termination alongside digital outputs
    FTA-E-02 Field Termination Assembly Alternative termination for SIC-to-field wiring

    FAQs

    Q1: What is the primary function of the FTA-T-02?
    A: It serves as a Field Termination Assembly (FTA), providing the physical interface between Honeywell system interconnection cables (SICs) and external field wiring. It routes 24 fail-safe digital output channels to field devices such as relays, solenoids, and valves.

    Q2: What does “fail-safe” mean for this module?
    A: In the event of a system power loss, communication failure, or internal hardware fault, the FTA-T-02 ensures output channels automatically revert to a predefined safe (de-energized) state. This prevents unintended activation of field equipment in safety-critical applications.

    Q3: How are the 24 channels organized?
    A: The 24 channels are arranged into 6 groups of 4 channels each. Six System Interconnection Cable connectors are labeled 1A, 1B, 2A, 2B, 3A, and 3B. This grouping architecture allows for localized circuit isolation and easier troubleshooting.

    Q4: What field wiring connections does it support?
    A: The module uses screw terminals with a maximum wire diameter of 2.5 mm² (AWG 14), a strip length of 7 mm, and a tightening torque of 0.5 Nm. It supports 24/48/60 VDC output applications.

    Q5: What safety certifications does the FTA-T-02 hold?
    A: The module is certified with CE and UL approvals, ensuring compliance with international safety and quality standards for industrial automation and safety instrumented systems.