Honeywell 51304386-100 MU-PPIX02 Pulse Input IOP, 8-Channel, UCN

The Honeywell 51304386-100 is the MU-PPIX02 Pulse Input Input/Output Processor (IOP) for the Honeywell TDC 3000 / TPS / Experion PKS Universal Control Network (UCN). It captures high-speed pulse and frequency signals from field devices such as flowmeters, tachometers, and encoders, converting them into digital counts for flow totalization, speed calculation, and equipment diagnostics within the DCS.

  • Item No :

    51304386-100
  • Order(MOQ) :

    1
  • Payment :

    EXW
  • Product Origin :

    USA
  • Shipping Port :

    Wuhan, Hubei, China
  • Lead Time :

    3-5 days
  • Weight :

    0.5KG
  • Products Description

    Honeywell 51304386-100 MU-PPIX02 new and original in stock

    Model Number 51304386-100 MU-PPIX02
    Place of Origin USA
    Dimension/Weight 0.5 kg
    Condition new and original
    Warranty 1 year
    Shipping term
    DHL Fedex TNT EMS UPS
    Payment TT / Western Union
    Delivery Time 3-5 days
    Service
    24 Hours Online Service

    CC-TUIO31

    Our Advantage

    Competitive Price

    For our original products, every product has a good discount.

    Professional Sales Team

    We have a sales team with strong professional knowledge and rich experience.

    Fast Delivery

    We have large warehouse for goods.Keep lots of goods in warehouse. so we could promise fast delivery.

     

      

    Applications

    • Flow measurement — pulse output from turbine, positive displacement, and electromagnetic flowmeters for totalization and batching .

    • Speed and overspeed protection — tachometer and magnetic pickup signals for turbine, compressor, and motor speed monitoring .

    • Custody transfer metering — high-accuracy pulse counting for fiscal measurement applications .

    • Equipment diagnostics — pulse-based condition monitoring of rotating machinery.

    • Legacy TDC 3000 / TPS maintenance — replacement and spare parts for existing UCN installations.


    FAQ

    Q1: What is the Honeywell 51304386-100 (MU-PPIX02) used for?
    It is an 8-channel Pulse Input IOP for Honeywell TDC 3000 / TPS / Experion PKS UCN systems. It captures pulse and frequency signals from flowmeters, tachometers, and encoders, converting them into digital counts for flow totalization, speed calculation, and diagnostics .

    Q2: How many channels does it have?
    8 independent pulse input channels .

    Q3: What is the frequency range?
    Per one detailed source, 0.1 Hz to 25 kHz per channel . Another source cites 1 Hz to 20 kHz . Verify against official documentation.

    Q4: Does it support redundancy?
    No. Redundancy is not supported for the MU-PPIX02 .

    Q5: What FTAs are compatible with the MU-PPIX02?
    Compatible FTAs include MU-TPIX12, MU-TPIX52, MC-TPIX12, and MC-TPIX52 .

    Q6: Is this a UCN IOP or a compact field module?
    It is a UCN card-cage IOP installed in the controller rack. Several third-party listings incorrectly describe it as a compact IP65 field module with RS-485 and relay outputs . Disregard those descriptions.

    Q7: What is the difference between 51304386-100 and 51304386-150?
    The -100 (MU-PPIX02) is the standard non-coated version. The -150 (MC-PPIX02) is the conformally coated version for harsh environments .

    Q8: Is this a current or legacy product?
    The TDC 3000 / TPS is a legacy/mature platform. The MU-PPIX02 is primarily available as spare or refurbished stock. Confirm availability with Honeywell or an authorized distributor.

    Q9: Where can I get technical documentation?
    Official Honeywell documentation, or an authorized distributor, is the authoritative source for specifications and compatibility. Note that third-party listings contain severely conflicting and inaccurate data.


    Recommending Models

     
     
    Model Description When to Choose
    51304386-100 (MU-PPIX02) Pulse Input IOP, 8-channel, standard (non-coated) When standard pulse acquisition is required for UCN installations
    51304386-150 (MC-PPIX02) Pulse Input IOP, 8-channel, conformally coated When conformal coating is required for harsh environments
    MU-TPIX12 / MC-TPIX12 Pulse Input FTA, compression terminals, 8 points Field termination for the MU-PPIX02 (MU- = uncoated, MC- = coated)
    MU-TPIX52 / MC-TPIX52 Pulse Input FTA, screw terminals, 8 points Field termination with screw terminals instead of compression