Q1: What is the primary function of the 2711P-T12C6A1?
It is a PanelView Plus 1250 operator terminal that provides a graphical user interface for controlling and monitoring industrial processes. Operators use the 12.1-inch touchscreen to interact with the HMI application, which is developed using FactoryTalk View Machine Edition software.
Q2: Is this terminal still in production?
No. The 2711P-T12C6A1 has been discontinued by Rockwell Automation. It is now available only through aftermarket suppliers offering surplus or refurbished units. The recommended migration path is to the PanelView Plus 6 (e.g., 2711P-T12C4D8) or PanelView Plus 7 series terminals.
Q3: What communication protocols does this terminal support?
The terminal has integrated DH+/DH-485/RIO communication as its primary legacy protocol, making it ideal for interfacing with vintage SLC and PLC-5 controllers. It also includes Ethernet, RS-232, and two USB ports for flexible connectivity.
Q4: What is the power requirement for this terminal?
The terminal requires 85–264V AC input power at 47–63 Hz. Maximum power consumption is 160 VA, with typical consumption at 65 VA.
Q5: What software is required to program this terminal?
The terminal is configured using FactoryTalk View Studio (Machine Edition). The logic module comes pre-installed with FactoryTalk View ME software and includes 64 MB each of Flash and RAM memory.