Q1: What is the primary function of the 2711P-T10C15A1?
It is a PanelView Plus 1000 operator terminal that provides a graphical user interface for controlling and monitoring industrial processes. Operators use the 10.4-inch touchscreen to interact with the HMI application, which is developed using FactoryTalk View Machine Edition software.
Q2: Is this terminal still in production?
No. The 2711P-T10C15A1 has been discontinued by Rockwell Automation since December 31, 2012. It is now available only through aftermarket suppliers offering surplus or refurbished units. The recommended migration path is to the PanelView Plus 6 or PanelView Plus 7 series terminals.
Q3: What communication protocols does this terminal support?
The terminal has integrated ControlNet communication as its primary protocol, supporting scheduled and unscheduled access to controller data, redundant cabling, and symbolic CIP addressing when communicating with a ControlLogix system. It also includes Ethernet (EtherNet/IP), RS-232 (DF1, DH-485), and two USB ports for flexible connectivity.
Q4: What is the power requirement for this terminal?
The terminal requires 85–264V AC input power at 47–63 Hz. Maximum power consumption is approximately 50 VA. The AC version (A1 suffix) includes an integrated power supply, whereas the D1 version is strictly DC-powered.
Q5: What software is required to program this terminal?
The terminal is configured using FactoryTalk View Studio (Machine Edition). The logic module comes with 64 MB each of Flash and RAM memory for application storage, with approximately 25 MB available for user applications.