Siemens 3RV2011-1KA10 SIRIUS Motor Protection Circuit Breaker

The Siemens 3RV2011-1KA10 is a SIRIUS 3RV2 series motor protection circuit breaker designed for reliable overload and short-circuit protection of three-phase motors. It features an adjustable overload release (A-release) range of 9–12.5 A, a fixed short-circuit release (N-release) at 163 A, and Class 10 tripping characteristics. The unit uses screw terminals for main circuit connections and belongs to the compact Size S00 frame.

  • Item No :

    3RV2011-1KA10
  • Order(MOQ) :

    1
  • Payment :

    EXW
  • Product Origin :

    Germany
  • Shipping Port :

    Wuhan, Hubei, China
  • Lead Time :

    3-5 days
  • Weight :

    0.350kg
  • Product Overview

    3RV2011-1KA10 SIMATIC Controller Module

    New in stock     

    Origin from Germany

    Payment Method: TT.Western Union

    Shipping Method: DHL\UPS\Fedex\EMS\Others

     

    More Brands

     
    Our Services

     

    FAQ

    Q1: What is the Siemens 3RV2011-1KA10?

    It is a SIRIUS 3RV2 motor protection circuit breaker with an adjustable overload range of 9–12.5 A, a 163 A magnetic short-circuit release, and Class 10 tripping. It uses screw terminals in the compact S00 frame .

    Q2: Is this product still in production?

    Yes. It is classified under Siemens PLM status PM300: Active Product, ensuring ongoing availability and support .

    Q3: What is the overload adjustment range?

    The A-release is adjustable from 9 to 12.5 A .

    Q4: What is the short-circuit release rating?

    The N-release is fixed at 163 A (magnetic) .

    Q5: What is the motor power rating?

    The breaker is rated for 5.5 kW at 400 V AC in AC-3 duty (12.5 A), and 3 kW at 230 V AC .

    Q6: Does this breaker include auxiliary contacts?

    No. The basic unit has 0 NO + 0 NC auxiliary contacts. Auxiliary switch blocks can be added as accessories .

    Q7: What type of terminals does it use?

    It uses screw terminals. For spring terminals, the 3RV2011-1KA20 variant is available .

    Q8: What is the short-circuit breaking capacity?

    The Icu is 100 kA at 240 V and 400 V AC .

    Q9: What are the dimensions and weight?

    Approximately 45 × 97 × 97 mm (W × H × D) and 0.350 kg .

    Q10: What is the country of origin?

    Germany .

    Q11: What should I verify before ordering?

    Always verify the exact part number (3RV2011-1KA10 for screw terminal vs. 1KA20 for spring terminal vs. 1KA40 for ring lug), confirm your motor full-load current falls within the 9–12.5 A range, check that the 163 A short-circuit release is appropriate for your application, and ensure your contactor is compatible (S00 or S0 frame) .

    Hot Sale Recommendation
     
    6ES7960-1AA06-0XA0 6SE7090-0XX85-1DA0
    6ES7321-1BL00-0AA0 6SE7024-7FD84-1HH0
    6ES7332-5HD01-0AB0 6ES7223-1PL22-0XA0
    6ES7331-7NF00-0AB0 6ES7214-1AG40-0XB0
    6ES7151-8AB01-0AB0 6ED1052-1FB00-0BA5
    6GK7443-1EX30-0XE0 6EP1334-2AA01
    6AV2123-2GA03-0AX0 6SE6400-1PB00-0AA0
Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.