The Siemens 6ES7416-2XP07-0AB0 is a SIMATIC S7-400 CPU 416-2 central processing unit, designed for high-performance automation applications in manufacturing and process industries. It features 8 MB of work memory (4 MB code + 4 MB data) and two integrated RS-485 interfaces (MPI/DP and PROFIBUS DP), enabling flexible communication with distributed I/O and field devices.

  • Item No :

    6ES7416-2XP07-0AB0
  • Order(MOQ) :

    1 Piece
  • Payment :

    EXW
  • Product Origin :

    Germany
  • Shipping Port :

    Wuhan
  • Lead Time :

    3~5 days
  • Weight :

    3kg
    • Product Details

       
       
      Specification Description
      Manufacturer Siemens
      Model 6ES7416-2XP07-0AB0
      Product Family SIMATIC S7-400
      Product Type CPU 416-2 Central Processing Unit
      Work Memory 8 MB (4 MB code + 4 MB data) 
      Integrated Load Memory 1 MB RAM 
      Expandable Load Memory FEPROM (FLASH) up to 64 MB; RAM up to 64 MB via Memory Card 
      Processing Times Bit: 12.5 ns; Word: 12.5 ns; Fixed-point: 12.5 ns; Floating-point: 25 ns 
      Interface 1 MPI/PROFIBUS DP, 12 Mbit/s 
      Interface 2 PROFIBUS DP, max. 12 Mbit/s 
      Number of RS-485 Interfaces 2 
      Max. DP Devices 32 per interface (125 for DP master total) 
      Max. I/O Address Area 16 KB inputs / 16 KB outputs 
      Max. Digital I/O 131,072 inputs / 131,072 outputs 
      Max. Analog I/O 8,192 inputs / 8,192 outputs 
      S7 Counters 2,048 
      S7 Timers 2,048 
      Data Blocks (DB) Max. 10,000; max. 64 KB each 
      Function Blocks (FB) Max. 5,000; max. 64 KB each 
      Backplane Current Draw 0.9 A typical @ 5 V DC; 1.1 A max. 
      Power Loss Typ. 4.5 W; Max. 5.5 W 
      Backup Battery Yes, all data buffered; typ. 180 µA backup current 
      Dimensions (H x W x D) 290 mm x 25 mm x 219 mm 
      Weight Approx. 0.896 kg 
      Engineering Software STEP 7 V5.5 or higher
      Country of Origin Germany
      Lifecycle Status PM300: Active Product 

      Related Product Model Recommendations

       
       
      Model Description Typical Application
      6ES7416-2XP07-0AB0 (this model) CPU 416-2, 8 MB, MPI/DP + PROFIBUS DP High-performance standard automation
      6ES7416-2FP07-0AB0 CPU 416F-2, 8 MB, fail-safe (F) version Safety-related applications up to SIL3 
      6ES7416-2XK04-0AB0 CPU 416-2, 2.8 MB (1.4 MB code + 1.4 MB data) Lower-memory alternative 
      6ES7416-2XN05-0AB0 CPU 416-2, earlier generation, 512 KB Legacy replacement (obsolete) 
      6ES7416-3ES07-0AB0 CPU 416-3, 16 MB, PN/DP version (PROFINET) Applications requiring PROFINET 
      6ES7416-3FS07-0AB0 CPU 416F-3 PN/DP, 16 MB, fail-safe + PROFINET Safety + PROFINET applications
      6ES7952-1AS00-0AA0 16 MB RAM Memory Card Load memory expansion

       

       

      FAQs

       

      Q1: What is the primary function of the 6ES7416-2XP07-0AB0?

      It is a high-performance central processing unit for the SIMATIC S7-400 automation system. It executes user programs, manages I/O communication via two RS-485 interfaces (MPI/DP and PROFIBUS DP), and provides extensive diagnostic capabilities. It is designed for complex industrial processes requiring large memory and fast processing .

      Q2: What is the difference between the 6ES7416-2XP07-0AB0 and the 6ES7416-2XK04-0AB0?

      The 2XP07 has 8 MB work memory (4 MB code + 4 MB data), while the 2XK04 has 2.8 MB (1.4 MB code + 1.4 MB data). Both CPUs share the same MPI/DP and PROFIBUS DP interfaces and processing speed. The 2XP07 is the higher-memory variant for larger programs .

      Q3: What software is required to program this CPU?

      The CPU requires STEP 7 V5.5 or higher (STEP 7 Classic). It is programmed using the SIMATIC Manager environment. It is not directly configurable in TIA Portal .

      Q4: Can this CPU be used in redundant (H) systems?

      No. The 6ES7416-2XP07-0AB0 is a standard (non-redundant) CPU. For redundant high-availability applications, the CPU 417-5H series (e.g., 6ES7417-5HT06-0AB0) is required, which supports S7-400H fault-tolerant configurations.

      Q5: What are the key communication capabilities?

      The CPU supports MPI (44 connections, 12 Mbit/s), PROFIBUS DP Master (32 connections per interface), S7 communication (client and server), S7 routing, and global data communication. It also supports isochronous mode and SYNC/FREEZE for precise motion control applications

Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.