Brand New Bently Nevada 3500/34-01-00 Triple Modular Redundant (TMR) Relay Module

The Bently Nevada 3500/34-01-00 is a Triple Modular Redundant (TMR) Relay Module for the 3500 series machinery protection system. It consists of two half-height TMR Relay Modules and one full-size TMR Relay I/O Module, working together with a dedicated TMR Rack Interface Module and three monitor modules to provide 2-out-of-3 voting for critical relay outputs.

  • Item No :

    3500/34-01-00
  • Order(MOQ) :

    1 Piece
  • Payment :

    EXW/CIF
  • Product Origin :

    USA
  • Shipping Port :

    Wuhan
  • Lead Time :

    3-5days
  • Weight :

    3kg
  • Product Details

     
     
    Specification Description
    Manufacturer Bently Nevada (Baker Hughes)
    Model 3500/34-01-00
    Product Family 3500 Machinery Protection System
    Product Type TMR Relay Module (2 half-height modules + 1 full-size I/O module) 
    Number of Relay Channels 4 channels 
    Relay Configuration 12 relays total (4 channel groups × 3 relays each) 
    Voting Logic 2-out-of-3 (2oo3) relay voting per channel 
    Relay Type Three DPDT relays in SPST configuration 
    Contact Life 100,000 cycles at 1.5 A, 24 Vdc, or 1 A, 120 Vac 
    Arc Suppressor Not supported 
    Relay Operation Normally Energized (NE) 
    Power Consumption 9.6 W typical 
    LED Indicators OK, TX/RX, CH ALARM 
    Operating Temperature -30°C to +65°C (-22°F to +150°F) 
    Storage Temperature -40°C to +85°C (-40°F to +185°F) 
    Humidity 95%, non-condensing 
    Relay Module Dimensions 120.4 mm x 24.6 mm x 241.8 mm 
    Relay Module Weight 0.34 kg (0.74 lb) 
    I/O Module Dimensions 241 mm x 24.4 mm x 99.1 mm 
    I/O Module Weight 0.5 kg (1.0 lb) 
    Rack Space 1 half-height front slot (per relay module); 1 full-height rear slot (I/O module) 
    Country of Origin USA 

    Related Product Model Recommendations

     
     
    Model Description Typical Application
    3500/34-01-00 (this model) TMR Relay Module, 2oo3 voting, 4 channels Safety-critical machinery protection with TMR 
    125696-01 TMR Relay Module (half-height, main card) Spare/replacement relay module 
    125704-01 TMR Relay I/O Module (full-height) Spare/replacement I/O module 
    149986-02 Spare 4-Channel Relay Control Module (for 3500/32M) Standard (non-TMR) relay applications 
    125720-01 Spare 4-Channel Relay Output Module (for 3500/32M) Standard relay output (repair only) 
    125720-02 Spare 4-Channel Relay Output Module (hazardous/SIL) Hazardous area and functional safety 

    Payment & Delivery

    FAQs

    Q1: What is the primary function of the 3500/34-01-00?

    It is a TMR Relay Module that provides high-reliability relay outputs for safety-critical machinery protection applications. It uses three independent relays to drive a single relay output, working with a TMR Rack Interface Module and three monitor modules to provide 2-out-of-3 voting for inputs. This architecture ensures that a single component failure cannot disable critical equipment protection functions .

    Q2: How does the TMR voting logic work?

    The TMR Relay Module evaluates alarm signals from three independent data paths provided by three monitors. It generates three alarm contact signals and sends them to the TMR Relay I/O Module, which contains 12 relays arranged in four channel groups of three. For each channel, the three signals are fed to three separate relays, and the output is determined by 2-out-of-3 voting. If a data path's OK status is NOT OK, the corresponding alarm contact signal is invalidated .

    Q3: What is the difference between the 3500/34 and the standard 3500/32M relay module?

    The 3500/34 is the TMR version designed for the highest availability applications, using three independent relays and 2oo3 voting. The 3500/32M is a standard 4-channel relay module for non-TMR applications. Both are full-height modules, but the 3500/34 consists of two half-height relay modules plus one full-size I/O module .

    Q4: What are the contact ratings for the 3500/34?

    The relay contacts are rated for:

    • Maximum switched power: 60 W DC, 125 VA AC 

    • Maximum switched current: 2 A 

    • Maximum switched voltage: 150 Vdc, 220 Vac 

    • Minimum switched current: 100 mA @ 5 Vdc 

    • Contact life: 100,000 cycles 

    Q5: What are the typical applications for the 3500/34?

    It is used in gas turbine protection systems, compressor emergency shutdown logic, high-integrity safety interlock systems, power generation machinery protection, and other critical rotating equipment applications where redundancy is required.