Brand New Bently Nevada 125744-01 3500/20-02-02-00 Rack Interface Module

The Bently Nevada 125744-01 is a TMR (Triple Modular Redundant) Rack Interface Module (RIM) main card for the 3500 series machinery protection system. It serves as the primary communication interface for rack configuration, data retrieval, and integration with external monitoring software.

  • Item No :

    125744-01
  • Order(MOQ) :

    1 Piece
  • Payment :

    EXW/CIF
  • Product Origin :

    USA
  • Shipping Port :

    Wuhan
  • Lead Time :

    3-5days
  • Weight :

    3kg
  • Product Details

     
     
    Specification Description
    Manufacturer Bently Nevada (Baker Hughes)
    Model 125744-01
    Product Family 3500 Machinery Protection System
    Product Type TMR Rack Interface Module (RIM) Main Card
    Rack Position Slot 1 (adjacent to power supply) 
    Communication Standards RS-232 / RS-422 serial communications 
    Communication Protocol Bently Nevada proprietary protocol 
    Baud Rate 38.4 k baud maximum (auto baud capable) 
    RS-232 Cable Length 30 meters (100 feet) maximum 
    RS-422 Cable Length 1200 meters (4000 feet) maximum 
    TMR Function Real-time monitor channel comparison and voting 
    Compatible Processors TDXnet, TDIX, DDIX 
    Front Panel LEDs OK, TX/RX, TM, CONFIG OK 
    Address Switch 63 selectable rack addresses 
    Configuration Keylock RUN / PROGRAM mode selector 
    Power Consumption 4.75 W typical 
    Operating Temperature -30°C to +65°C (-22°F to +150°F) 
    Storage Temperature -40°C to +85°C (-40°F to +185°F) 
    Dimensions (H x W x D) 241.3 mm x 24.4 mm x 241.8 mm 
    Weight 0.91 kg (2.0 lb.) 
    Country of Origin USA 
    Lifecycle Status Active / Available as New Surplus 

    Related Product Model Recommendations

     
     
    Model Description Typical Application
    125744-01 (this model) TMR Rack Interface Module (main card) Triple Modular Redundant configurations 
    125744-02 Standard Rack Interface Module (main card) Standard (non-TMR) applications 
    125768-01 RIM I/O Module with RS-232/RS-422 Interface Companion I/O for serial communication 
    135031-01 RIM I/O Module with Modem Interface Companion I/O for modem communication 
    125760-01 Data Manager I/O Module Connect two communication processors to rack 
    3500/22M Transient Data Interface (TDI) Modern replacement with Ethernet/USB connectivity 
    3500/05 19-inch System Rack Physical housing for the RIM 
    3500/15 Power Supply Module Required companion for rack operation 

    Payment & Delivery

    FAQs

    Q1: What is the primary function of the 125744-01?

    It is the TMR Rack Interface Module (main card) for the 3500 series machinery protection system. It serves as the primary communication interface for rack configuration, data retrieval, and integration with external monitoring software. In TMR configurations, it performs real-time monitor channel comparison — continuously comparing outputs from three redundant monitors and flagging any monitor whose output differs from the other two beyond a configured percentage.

    Q2: Where must the 125744-01 be installed?

    The module must be installed in Slot 1 of the 3500 rack, adjacent to the power supply. Each 3500 rack requires exactly one RIM or TDI. The module provides certain common functions for the entire rack but is not part of the critical monitoring path .

    Q3: What is the difference between 125744-01 and 125744-02?

    The 125744-01 is the TMR Rack Interface Module (main card) that performs monitor channel comparison functions for Triple Modular Redundant configurations. The 125744-02 is the Standard Rack Interface Module (main card) for non-TMR applications. The TMR version is required when the rack is configured for triple redundancy.

    Q4: What is the TMR channel comparison function?

    In TMR configurations, the 3500 system requires a TMR version of the RIM. The TMR RIM continually compares a specified output of 3 redundant monitors. If it detects that information from one monitor is no longer equivalent (within a configured percent) to the remaining two, it flags that monitor as being in error and places an event in the System Event List .

    Q5: Does the 125744-01 affect the critical monitoring path?

    No. While the RIM provides certain common functions for the entire rack, it is not part of the critical monitoring path. The monitoring system's automatic machinery protection functions continue to operate normally even if the RIM is removed or fails. However, the RIM is essential for rack configuration, data retrieval, and system diagnostics.

Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.