Q1: What is the primary function of the 3500/20-02-02-00?
It is a TMR Rack Interface Module that serves as the primary communication interface for the 3500 rack, supporting Bently Nevada's proprietary protocol for rack configuration and machinery data retrieval. In TMR configurations, it performs real-time monitor channel comparison — continuously comparing outputs from three redundant monitors and flagging any monitor whose output differs from the other two beyond a configured percentage.
Q2: Can the 3500/20-02-02-00 be installed in any slot?
No. It must be installed in Slot 1, adjacent to the power supply. Each 3500 rack requires exactly one RIM or TDI. For TMR applications, two 3500/15 Power Supplies are required, and the rack jumper must be set to the TMR position.
Q3: What is the difference between 125744-01 and 125744-02?
The 125744-01 is the TMR Rack Interface Module (main card) that performs monitor channel comparison functions for Triple Modular Redundant configurations. The 125744-02 is the Standard Rack Interface Module (main card) for non-TMR applications. The TMR version is required when the rack is configured for triple redundancy.
Q4: What are the maximum cable lengths supported?
The 125768-01 supports maximum cable lengths of 30 meters (100 feet) for RS-232 and 1200 meters (4000 feet) for RS-422. For longer distances, RS-422 communication should be selected to prevent signal degradation.
Q5: Does the TMR RIM affect the critical monitoring path?
No. While the RIM provides certain common functions for the entire rack, it is not part of the critical monitoring path. The monitoring system's automatic machinery protection functions continue to operate normally even if the RIM is removed or fails. However, in TMR configurations, the TMR RIM performs essential monitor channel comparison to maintain high-integrity protection.